Page 37 of 40
METER -
advanced confi guration
9.8.3 - LANGUAGE
Position the cursor on LANGUAGE, press ENTER to access.
Sets the menu language: English, Italian, French
Press SCROLL to select the menu language.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
OUTPUT SAFE MODE
SET UID
LANGUAGE
FREQUENCY
F_WINDOW
RESTORE SETTING
►
ENGLISH
ITALIANO
FRANCAIS
►
9.8.4 - FREQUENCY
Position the cursor on FREQUENCY, press ENTER to access.
It’s possible to check the computed sensor emission frequency.
LEFT ARROW to exit without changes
OUTPUT SAFE MODE
SET UID
LANGUAGE
FREQUENCY
F_WINDOW
RESTORE SETTING
►
00.0 kHz
FREQUENCY
9.8.5 - F_ WINDOWS
Position the cursor on F_WINDOWS, press ENTER to access.
It is the increase value (in cm), step to step, of the window width during the
echo signal research phase.
The “F_WINDOWS” is the area where the echo reception is active.
Normally it is positioned around the real echo signal and all echoes detect-
ed within the F_WINDOW are deemed valid.
Example: F_WINDOW parameter set to 5.
- The METER detects an echo signal which is 4 meters from the sensor.
- Suddenly, the echo signal disappears and a new echo signal to 3.5 mt
away from the sensor is detected.
- Each time the echo signal will be emitted, the METER will enlarge
“F_WINDOW” with 5cm step, until covering the new eco detected area.
Now the F_WINDOW will start to tighten around the new echo signal and
the new measurement of 3,5mt distance will be used to calculate the level
measurement, alarm thresholds, etc..
F_WINDOW serves to fi lter false echo signals products, for example, by
the agitator blades
Range: 05÷20
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
Default value: 05 (2 wires versions) e 10 (4 wires versions)
OUTPUT SAFE MODE
SET UID
LANGUAGE
FREQUENCY
F_WINDOW
RESTORE SETTING
►
05
SET WIDTH