background image

ENGLISH

EN-2

1/2" 

3/8" 

Connecting the drain hose

• In the heating mode, the outdoor unit discharges water due to 

defrosting from its drain port and drain hole. Perform drain work if 
water drops are a problem. 

• In very cold areas where the water in the drain hose could freeze, do 

not use a drain hose and the base pan cap with the outdoor unit.

(1) Insert the base pan caps into the drain holes on the bottom of the 

outdoor unit.

(2) Fit the drain joint into the drain tray and insert drain tray to the drain 

port.

(3) Connect commercial drain hose to the drain joint. 

Installation dimension

Referring to the fi gure, fi rmly fasten the 
outdoor unit with bolts.

Install the indoor unit according to the following table.

Port 

Port size

Indoor unit class

D

Liquid

1/4" (ø 6.35 mm)

07   09   12

Gas

3/8" (ø 9.52 mm)

C

Liquid

1/4" (ø 6.35 mm)

07   09   12

Gas

3/8" (ø 9.52 mm)

B

Liquid

1/4" (ø 6.35 mm)

07*   09*   12*   15   18

Gas

1/2" (ø 12.7 mm)

A

Liquid

1/4" (ø 6.35 mm)

07*   09*   12*   15   18

Gas

1/2"(ø 12.7 mm)

1     OUTDOOR UNIT INSTALLATION

Drain hose (Commercially available)
Inside diameter: 5/8" (ø 16 mm)

Drain port

Drain tray  

3

Drain joint  

4

Note:

• Make sure the fl are nuts of the outdoor unit are securely closed for those not connected to the indoor unit.

• Install at least 3 indoor units. 
  Exceptionally, in the case of following combination, it is possible to install 2 units.

 15 class + 18 class
 18 class + 18 class

Joint (1/2" 

 3/8")

Seal ring

Flare nut (3/8")

Outdoor unit

Indoor unit

PORT SIZE OF THE OUTDOOR UNIT

Base pan cap  

2

Connecting the pipes

Connect the pipes for the indoor unit first and then for the 
outdoor unit. 

(1) Tighten the fl are nuts by hand for the fi rst 3-4 turns.

(2) Use a spanner and torque wrench to tighten up the pipes.

• Do not over tighten the pipes; it may be deformed or 

damaged. 

Notes:

• Bend the pipes carefully as not to damage them.
• Lay the drain hose below the pipes.

(4) Flaring 
 Flare 

processing 

dimensions(A)

(5) Checking
 To 

be 

fl ared perfectly circular.

 

Flare nut not missing.

Flare nut

Flaring the pipe end

(1) Cutting with a pipe cutter
 

Cut at a right angle.

(2) Deburring
 

Allow no cuttings in the pipe.

(3) Putting in the fl are nut

90°

A

Tool

A

R410A tool

0 - 0.02 inch
(0 - 0.5 mm)

Conventional tool

0.04 - 0.06 inch

(1.0 - 1.5 mm)

Spanner

Torque wrench

Flare nut tightening torque

Pipe size

Torque

Liquid side

1/4" (ø 6.35 mm)

11.8±1.5 ft·lbf (16±2 N·m)

Gas side

3/8" (ø 9.52 mm)

28.0±3.0 ft·lbf (38±4 N·m)

1/2" (ø 12.7 mm)

40.6±3.7 ft·lbf (55±5 N·m)

2     CONNECTING THE REFRIGERANT PIPES

* In the case of connecting 07, 09,12 class to the port A and B, 

use the reducer supplied with the unit as directed below.

Connecting a pipe of 3/8"(ø 9.52 mm) to the port for 
1/2"(ø 12.7 mm).

 

1.9 ft (590 mm)

1.2 ft (361 mm)

IM_A3AEX4M3PU(B434)_EN+FR+ES.indb   EN-2

IM_A3AEX4M3PU(B434)_EN+FR+ES.indb   EN-2

2/7/13   11:05:28 AM

2/7/13   11:05:28 AM

Summary of Contents for AE-X4M30PU

Page 1: ...EUR INDIVIDUEL EN DEUX PARTIES MANUEL D INSTALLATION ACONDICIONADOR DE AIRE TIPO SPLIT MANUAL DE INSTALACIÓN OUTDOOR UNIT AE X4M30PU ENGLISH FRANÇAIS ESPAÑOL IM_A3AEX4M3PU B434 _EN FR ES indb 1 IM_A3AEX4M3PU B434 _EN FR ES indb 1 2 7 13 11 05 27 AM 2 7 13 11 05 27 AM ...

Page 2: ... installation of outdoor unit only For the installation of the indoor unit see the installation manual accompanying indoor unit SAFETY PRECAUTIONS Tighten the flare nut with a torque wrench according to the specified method If the flare nut is tightened too hard the flare nut may be broken after a long time and cause refrigerant gas leakage When installing the unit take care not to enter air subst...

Page 3: ...ombination it is possible to install 2 units 15 class 18 class 18 class 18 class Joint 1 2 3 8 Seal ring Flare nut 3 8 Outdoor unit Indoor unit PORT SIZE OF THE OUTDOOR UNIT Base pan cap 2 Connecting the pipes Connect the pipes for the indoor unit first and then for the outdoor unit 1 Tighten the flare nuts by hand for the first 3 4 turns 2 Use a spanner and torque wrench to tighten up the pipes D...

Page 4: ...wrench Close it after 5 second and check for gas leakage 8 Disconnect the gauge manifold hose from the service port 9 Fully open the stop valve liquid side with hexagon wrench Turn all the way up to contact 10 Fully open the stop valve gas side with hexagon wrench Turn all the way up to contact 11 Firmly tighten the service port cap and both valve shaft caps with a torque wrench at the specified t...

Page 5: ...leted normally all LED will flash simultaneously and the operation will stop Wire check time 10 20 minutes When self correction can not done all LED will indicate triple flash for eight times and the operation will stop Check and correct following points Check all pipings are connected Check the stop valves are open After correction repeat the wire check again If error is still detected or other t...

Page 6: ...onnect the gauge manifold hose to the service port of the stop valve gas side 2 To start pump down press the PUMP DOWN button SW1 for 5 seconds or more The OPERATION lamp on the indoor unit will flash and three BEEP will be emitted 3 After 5 10 minutes fully close the stop valve liquid side 4 Close the stop valve gas side when the compound gauge reading becomes almost 0 MPa 0 cmHg 5 To stop the pu...

Page 7: ...ENGLISH EN 6 IM_A3AEX4M3PU B434 _EN FR ES indb EN 6 IM_A3AEX4M3PU B434 _EN FR ES indb EN 6 2 7 13 11 05 33 AM 2 7 13 11 05 33 AM ...

Page 8: ...éfrigérant R410A Utilisez les tuyaux de réfrigérant l écrou évasé et les outils exclusive ment pour le R410A REMARQUES SUR LES EMPLACEMENTS 300 mm 1 pi ou plus L installation doit être faite en conformité avec le manuel d ins tallation par un technicien professionnel Un travail incorrect peut provoquer un choc électrique une fuite d eau un incendie Assurez vous d utiliser les accessoires et les pi...

Page 9: ... intérieures Exceptionnellement dans le cas de la combinaison suivante il est possible d installer 2 unités 15 classe 18 classe 18 classe 18 classe Joint 1 2 po 3 8 po Bague d étanchéité Écrou évasé 3 8 po Unité extérieure Unité intérieure DIMENSION DE L ORIFICE DE L UNITÉ EXTÉRIEURE Bouchon du plateau de base 2 Raccordement des tuyaux Raccordez les tuyaux pour l unité intérieure en premier puis c...

Page 10: ...es et vérifier s il y a des fuites de gaz 8 Débrancher le tuyau du manomètre de l orifice de l entretien 9 Ouvrir complètement la vanne d arrêt coté liquide avec une clé hexagonale Tournez vers le haut jusqu au contact 10 Ouvrir complètement la vanne d arrêt Côté gaz avec une clé hexagonale Tournez vers le haut jusqu au contact 11 Serrez fermement le bouchon de l orifice d entretien et des deux bo...

Page 11: ...les DEL clignotent simultanément et l opération s arrête Durée de la vérification de fil 10 20 minutes Lorsque la correction automatique ne peut pas se faire toutes les DEL indiqueront clignoteront 3 fois et ce huit fois puis l opération s arrêtera Vérifier et corriger les points suivants Vérifier si tous les tuyaux sont raccordés Vérifier si les vannes d arrêt sont ouvertes Après correction répét...

Page 12: ... arrêt côté gaz lorsque la mesure du manovacuomètre devient presque 0 MPa 0 cmHg 5 Pour arrêter la récupération du fluide appuyez sur la touche PUMP DOWN SW1 pendant au moins 5 secondes 6 Débrancher le tuyau du manomètre de l orifice de l entretien PROCÉDURE SANS UTILISER LE MANOMÈTRE DE PRESSION 1 Pour commencer la récupération du fluide appuyez sur la touche PUMP DOWN SW1 pendant au moins 5 seco...

Page 13: ...FR 6 FRANÇAIS IM_A3AEX4M3PU B434 _EN FR ES indb FR 6 IM_A3AEX4M3PU B434 _EN FR ES indb FR 6 2 7 13 11 05 40 AM 2 7 13 11 05 40 AM ...

Page 14: ... describe solo la instalación de la unidad exterior Para la instalación de la unidad interior vea el manual de instalación que se adjunta con la unidad interior PRECAUCIONES DE SEGURIDAD Ajuste la tuerca cónica con una llave de torsión según el método indicado Si la tuerca cónica está demasiado ajustada podría rajarse o romperse después de un tiempo y producir pérdida de gas refrigerante Cuando in...

Page 15: ...ción siguiente es posible instalar 2 unidades Clase 15 clase 18 Clase 18 clase 18 Junta 1 2 3 8 Anillo de sellado Tuerca cónica 3 8 Unidad exterior Unidad interior TAMAÑO DE LA ABERTURA DE LA UNIDAD EXTERIOR Tapa para bandeja base 2 Conectar los caños Conecte los caños de la unidad interior primero y luego los de la unidad exterior 1 Ajuste las tuercas a mano las primeras 3 4 vueltas 2 Utilice una...

Page 16: ...gas 8 Desconecte la manguera del manómetro de la abertura de servicio 9 Abra completamente la válvula de cierre lado del líquido con una llave hexagonal Gírela del todo hasta el contacto 10 Abra completamente la válvula de cierre lado del gas con una llave hexagonal Gírela del todo hasta el contacto 11 Ajuste firmemente la tapa de la abertura de servicio y las dos tapas de los ejes de válvula con ...

Page 17: ...simultáneamente y el funcionamiento se detendrá Periodo de verificación del alambre 10 20 minutos Cuando la autocorrección no se pueda realizar todos los LED indicarán un triple parpadeo ocho veces y el funcionamiento se detendrá Compruebe y corrija los siguientes puntos Compruebe que todas las cañerías estén conectadas Compruebe que las válvulas de cierre estén abiertas Después de la corrección r...

Page 18: ...rvicio de la válvula de cierre lado del gas 2 Para poner en marcha la evacuación presione el botón PUMP DOWN SW1 durante 5 segundos o más La luz de FUNCIONAMIENTO de la unidad interior parpadeará y se emitirán tres PITIDOS 3 Tras 5 10 minutos cierre completamente la válvula de cierre lado del líquido 4 Cierre la válvula de cierre lado del gas cuando la lectura del manómetro compuesto sea casi 0 MP...

Page 19: ...ES 6 ESPAÑOL IM_A3AEX4M3PU B434 _EN FR ES indb ES 6 IM_A3AEX4M3PU B434 _EN FR ES indb ES 6 2 7 13 11 05 47 AM 2 7 13 11 05 47 AM ...

Page 20: ...Printed in Thailand TINS B434JBRZ 13A TH 1 IM_A3AEX4M3PU B434 _EN FR ES indb ES 7 IM_A3AEX4M3PU B434 _EN FR ES indb ES 7 2 7 13 11 05 47 AM 2 7 13 11 05 47 AM ...

Reviews: