SIM426-010

 

 

 

problems  such  as  animal  biting,  electricity  leakage  in 
puddle. 

19.  Take  proper  measures  for  preventing  the  laminate 

(consisted  of  resin,  cells,  glass,  back  sheet,  etc.)  from 
dropping out of the frame in case the glass is broken. 

20.  Cables shall be located so that they will not be exposed to 

direct  sunlight  after  installation  to  prevent  degradation  of 
cables.

 

21. 

If  batteries  are  used  with  modules,  follow  safety 

precautions of the battery manufacturer.

 

22. 

In case of extreme snow build-up, the weight of the snow 

may cause the module’s frame to deform. Take appropriate 

preventive  measures  to  minimize  any  possible  resulting 

damage. 

 

4. SITE SELECTION

 

In most applications, the PV modules should be installed in a 

location where there is no shading throughout the year. In the 
Northern Hemisphere, the PV modules should typically face  
south, and in the Southern Hemisphere, the PV modules should 
typically face north. 

Please  make  sure  that  there  are  no  obstructions  in  the 

surroundings of the site of installation. TAKE PROPER STEPS 
in order to maintain reliability and safety, in case the PV modules 
are used in areas such as: Heavy snow areas / Extremely cold 
areas / Strong wind areas / Installations over, or near, water / 
Areas 

where 

installations 

are 

prone 

to 

salt 

water 

damage/corrosive  gas  environment/  Small  islands  or  desert 
areas. 

The results of the ammonia test and the salt-mist-corrosion test 

on  the  modules,  carried  out  under  such  strict  test  conditions, 
should be disclosed for reference purposes only. The decision 
on  whether the modules are suitable and compatible for each 
instal

lation  field  will  depend  on  the  user’s  judgement  and 

responsibility. 

 

5. TILT ANGLE 

The tilt angle is the measurement between the PV module and 

a  horizontal  ground  surface.  The  PV  module  generates  the 
maximum output power when it faces the sun directly.  
5 degrees or more is recommended for the tilt angle of the PV 
module for the maintenance. (See 9. Maintenance) 

For  the  standalone  systems  with  a  battery  where  the  PV 

modules are attached to a permanent structure, the tilt angle of 
the  PV  modules  should  be  determined  to  optimize  the 
performance when the sunlight is the scarcest. In general, if the 
electric power generation is adequate when the sunlight is the 
scarcest, then the angle chosen should be adequate during the 
rest of the year. For grid-connected installations where the PV 
modules  are  attached  to  a  permanent  structure,  it  is 
recommended  to  tilt  the  PV  module  at  the  angle  equal  to  the 
latitude of the installation site so that the power generation from 
the PV module will be optimum throughout the year. 
 

6. WIRING 

To  ensure  proper  system  operation  and  to  maintain  your 

guaranty, observe the correct cable connection polarity (Figures 
1  &  2)  when  connecting  the  modules  to  a  battery  or  to  other 
modules. If not connected correctly, the bypass diode could be 
destroyed. 

PV  modules  can  be  wired  in  series  to  increase  voltage. 

Connect wires from the positive terminal of one module to the 
negative terminal of the next module. Figure 1 shows modules 
connected in series. 

Connect PV modules in parallel to increase current. Connect 

wires  from  the  positive  terminal  of  one  module  to  the  positive 
terminal  on  the  next  module.  Figure  2  shows  modules 
connected in parallel. 
 
 
 
 
 
 
 
 
 
 
 
 

7. GROUNDING 

The frame grounding must consider the local requirement and 

regulation at the  installation site. When grounding is required, 
please refer to below example connection (Figure 3).  Please be 
careful in arranging  the system ground so that the removal of 
one  module  from  the  circuit  will  not  interrupt  the  grounding  of 
any other modules. 

The modules should be grounded to the same electrical point 

as described below. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You  can  use  a  hole  with  the  appropriate  symbol  for 

equipotential bonding on the side frame for either a bolt, nut and 
washer  grounding  the  module  to  the  frame,  a  ground  lug 
fastened by bolt or screw, or appropriate screw (hardware not 
provided). An example of acceptable ground connection using 
a bolt, nut and washer retaining a ground lug is shown in figure 
3. In a connection of this type, the hardware (such as a toothed 
locked washer / star washer) must score  the frame surface to 
make positive electrical contact with the frame. The ground wire 
must  be  considered  within  the  local  requirement  of  local  and 
regulation at the site of installation. 
 

8. MOUNTING 

Please  make  sure  that  all  the  information  described  in  the 

installation manual is still valid and proper for your installation. 
The mounting method  has been verified by SHARP and NOT 
CERTIFIED by a third party organization. 

The approved way to mount Sharp PV modules to a support 

structure  is  described  in  this  INSTALLATION  MANUAL. 
Although  Sharp  does  not  specify  or  warrant  frame  clips  or 
clamps,  using  frame  clips  (not  provided)  or  clamps  (not 
provided) is  possible  when they are designed for PV modules 
and  with  minimum  dimensions  on  the  sides  of  the  module  in 
accordance with the instructions and drawings provided. If using 
frame clips or clamps, the modules should be fixed rigidly and 
there shall be no damage to the modules by deforming mounting 
structure against design load.  

The Sharp module guaranty may be void if customer-selected 

frame  clips  are  improper  or  inadequate  for  module  properties 
(including strength or material) or installation. Note that if metal 
clips are used, there must be a path to ground from the clips, 
(for instance, using star washers in the clip hardware set). 
Please  review  the  descriptions  and  drawings  carefully;  not 
mounting the modules according to one of these methods may 
void your  guaranty. These mounting methods are designed to 
allow  module  loading  of  2400Pa.  The  module  has  passed  a 
snow  load  test  of  5400Pa  according  to  IEC61215.  Support 
structures  that  PV  modules  are  mounted  on  should  be  rigid. 
Sharp  PV  modules  are  designed  to  ensure  optimal  electrical 
performance under the condition that they are mounted on rigid 
support  structures.  Deformation  of  support  structure  may 
damage PV module with its electric performance. 
When mounting the module on structure, ensure that no corner 
has a displacement of more than 2mm per every 1000mm of the 
diagonal. 
 

9. MAINTENANCE 

The modules are designed for long life and require very little 

maintenance. If the angle of the PV module is 5 degrees or more, 
normal  rainfall  is  sufficient  to  keep  the  module  glass  surface 
clean under most weather conditions. If dirt build-up becomes 
excessive, clean the glass surface preferably with water only, or 
with wet soft sponge or cloth in case to remove stubborn dirt. If 
cleaning the back  of the module is required, take  utmost care 
not to damage the back side materials. In order to ensure the 
operation of the system, check the connection of wiring and the 
state of the jacket of wires occasionally.

SIM201-004 

Summary of Contents for NU-AH370

Page 1: ...dically remove any overhanging snow and or ice from the module framework as it may cause deformation of the module frame GENERAL INSTRUCTIONS 1 INTRODUCTION This Installation Manual contains essential information for the electrical and mechanical installation that you must know before installing SHARP PV modules This also contains safety information you need to be familiar with All the information...

Page 2: ...In case of parallel connection please be sure to take proper measure e g fuse for protection of module and cable from over current and or blocking diode for prevention of unbalanced strings voltage to block the reverse current flow The current may easily flow in a reverse direction 20 Keep modules away from children HANDLING SAFETY 1 Do not cause an excessive load on the surface of PV module or tw...

Page 3: ...rame grounding must consider the local requirement and regulation at the installation site When grounding is required please refer to below example connection Figure 3 Please be careful in arranging the system ground so that the removal of one module from the circuit will not interrupt the grounding of any other modules The modules should be grounded to the same electrical point as described below...

Page 4: ...ic modules properly For Information about the proper disposal contact your local recycling site ELECTRICAL OUTPUT AND THERMAL CHARACTERISTICS Rated electrical characteristics of Isc Voc are within 10 percent of the indicated values and 5 0 percent of Pmax power measurement tolerance 3 under STC standard test conditions irradiance of 1000 W m2 AM 1 5 spectrum and a cell temperature of 25 C 77 F Tab...

Reviews: