SJPT55RHS
7 – 4
(DEF-thermistor system diagnosis)
Power OFF
Replace DEF-thermistor.
Replace main PWB.
NG?
NG?
NO
NO
YES
YES
Remove 6P connector from E.V.
cover Assy and measure the
thermistor resistance between
and
.
03 /
63
04 /
64
(Outside temperature - thermistor system diagnosis)
Replace Main-PWB.
Outside
temperature thermistor
is installed on
Main-PWB ass'y.
(Defrosting diagnosis)
07
Replace main PWB.
Replace fuse Assy.
Replace
defrost heater.
NO
YES
NO
YES
YES
NO
YES
NO (Open)
Forced defrosting (Measurement is impossible when
DEF-thermistor is set at 10°C or higher because
defrosting ends immediately)
After approx. 15 sec., the voltage
measured across
and
of CN5
on the main PWB is equal to supplied
voltage? (e.g. 240 V)
Disconnect CN5 from the main PWB. Measure the
resistance between
and
of CN on the wiring.
Check defrost heater wiring for loose
connection or disconnection.
Check cause of defrosting failure
· Check door packing
· Check mounting seal of E.V. cover Assy
[3]
[4]
[5]
5.8
approx. 280
(defrost heater 170~190W)
10
5
6
8
10
Turn power OFF. After approx. 30 sec.,
open door and re-energize.
(Buzzer beeps continuously)
8
10
Between 6P connector 2 and
4P connector 1 ( white line) on
E.V. cover Assy is carrying current?
Resistance of 4P connector between
1 and 2 on E.V. cover K is normal? (331
)