3 Function parameter schedule graph
11
code
default
ication
F2.00
Analog filter time
constant
0.00
-
30.00s
0.01s 0.20s
○
F2.01
Forward reverse run
dead-section time
0.0
-
3600.0s
0.1s 0.1s
○
F2.02 Automatic energy
save run
0: no action
1: action
1 0
×
F2.03 AVR function
0: no action
1: action all the time
2: no action only during Dec
1 0
×
F2.04
Slip frequency
compensation
0
~
150(
%
)0-no slip frequency
compensation
1 0
×
F2.05 Carrier wave
freq.
1
-
10.0K
0.1K
depend on
machine type
×
F2.06 Jog run frequency
0.10
-
50.00Hz
0.01Hz 5.00Hz
○
F2.07 Jog Acce time
0.1
-
60.0s
0.1s 20.0s
○
F2.08 Jog Dece time
0.1
-
60.0s
0.1s 20.0s
○
F2.09 reserved
1
0
×
F2.10
Principal subordinate
Machine communication
frequency provision
proportion
0
(%)-
500
(%)
1(%) 100(%)
○
F2.11 LED display
control 1
0000-1111
first bit: running time
0: not display
1: display
second bit: accumulative time
0: not display
1: display
third bit: input terminal status
0: not display
1: display
kilobit(fourth bit): output terminal status
0: not display
1: display
1 1111
○
F2.12 Reserved
F2.13 Parameter operation
control
LED 1st bit:
0: all parameter allowed to be modified
1: except this parameter
,
all other parameter
not allowed to be modified
2: except F0.01 and this parameter
,
all other
parameter not allowed to be modified
LED 2nd bit:
0: no action
1: restore default value
2: clear history failure record
LED 3rd bit:
0: lock all buttons
1: lock all buttons but not STOP key
1 0
×