DATA SHEET

 

 

  Note: Specifications are subject to change without notice   

 

 

                                                                                                                                                               

 

 

Features 

 

Twin LED for 360° view.   

 

Electronically addressed in field. 

 

Built-in microprocessor stores 14 history data. 

 

Rate of rise and fixed temperature alarm modes. 

 

Self-diagnostic. 

 

Remote indicator output available. 

 

Complies with EN 54-5 standard.

 

Description   

D-A412  Intelligent  Rate  of  Rise  and  Fixed 
Temperature  Heat  Detector  is  an  addressable  fire 
alarm  device  cooperating  with  SHIELD  intelligent  fire 
alarm control panels to build a fire detection system.   

The detector shows fire alarm by the LED indicators. It 
uses thermistor as its sensor and transmits the signal 
to  a  microprocessor  which,  after  voltage  transfer, 
processes  the  signal  using  intelligent  arithmetic  and 
sends  any  fire  alarm  to  the  control  panel.  The  LED 
indicators will then be lit by the control panel.   

Connection and Cabling 

Fig.1 shows the detector bottom and Fig. 2 the base.   

100mm

C

 

Fig. 1                                          Fig. 2 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 
2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 

Recommended Cabling 

1.0mm

2

  or  above  fire  cable  is  recommended  but 

subject to local codes.   

Installation 

A fixed installation direction is ensured by the location 
elements  on  the  detector  and  the  base.  Fix  the  base 
with two tapping screws, and then align mark C on the 
detector with A on the base, rotate the detector to align 
mark  C  with  mark  B  (Refer  to  Fig.1  and  2  for  the 
position of the marks),detector will be fitted to base. 
 

 

 

 
 
 
Note: The detector shall be horizontally installed. If 
it  has  to  be  installed  on  an  inclined  plane,  the 
inclination angle shall not be over 45

ºººº

.   

 

Fig. 3 shows the installation of the detector. 

Detector

Conduit

Back Box

 Base

 

Fig.3

 

Application 

The  detector  is  especially applicable to  places where 
fire  occurs  with  sharp  rise  of  temperature.  Used 
together  with  smoke  detectors,  it  can  detect  fire  with 
more reliability to reduce losses. 

The  detector  can  be  addressed  in  field  by  using 
D-APP programmer. Please refer to 

D-APP Hand Held 

Programmer  Installation  and  Operation  Manual 

for 

details. 

Maintenance 

1.  The  detector  should  be  installed  just  before 

commission  and  kept  well  before  installation, 
taken  corresponding  measures  for  dust-proof, 
damp-proof and corrosion-proof. 

 

D-A412 

Intelligent Rate of Rise 

 Fixed Temperature Heat Detector 

 

 

Addressable Fire Alarm System   