WARNINGS

The  SHIELD  sprinklers  must  be  installed  and  maintained 
in compliance with this document. Depressurize and drain 
the piping system before attempting to install, remove, 
or adjust any Sprinklers. Failure to do so may impair the  
performance of these sprinklers. The owner is responsible 
for  maintaining  the  fire  protection  system  and  devices  in 
operation.

WRENCH DESCRIPTION

The  Sprinkler  Wrench  is  a  tool  specifically  designed  for  
installing SHIELD Sprinklers. These special wrenches must 
be used to provide the proper leverage when tightening the 
sprinkler and to minimize slippage during installation. Any 
other wrench may damage the sprinkler. 

INSTALLATION

All SHIELD Sprinklers must be installed according to 
NFPA  13  Standards.  Deviations  from  these  requirements 
and standards or any alteration to the sprinkler itself will 
void  any  warranty  made  by  manufacturer.  In  addition, 
installation must also meet local government provisions, 
codes and standards as applicable. 

The  system  piping  must  be  properly  sized  to  insure  the 
minimum required flow rate at the sprinkler. Check for the 
proper  model,  style,  orifice  size  and  temperature  rating 
prior to installation. Install sprinklers after the piping is in 
place to avoid mechanical damage, replace any damaged 
units. Wet pipe systems must be protected from freezing.

Upon completion of the installation, the system must be 
tested per recognized standards. In the event of a thread 
task, remove the unit, apply new pipe joint compound or 
tape, and reinstall.

ADDITIONAL

Recessed  Sprinkler  -  To  install  the  escutcheon  plate, 
align with it and push or thread over the sprinkler body 
into the upper support piece, until the outer edge of the  
escutcheon meets the mounting surface.

INSTALLATION SEQUENCE

Step 1. The unit must be installed in the horizontal sidewall 
position for the Horizontal Sidewall Sprinklers.

Step 2. Use only a non-hardening pipe joint compound or 
tape seal. Apply only to the male threads.

Step 3. Hand tighten the sprinkler into fitting.

Step  4.  For  Horizontal  Sidewall  Sprinklers,  use  a  
standard wrench. Tighten the unit into the fitting. A lead-
tight  joint  requires  only  7  to  14ft.-lbs(9.5  to19.0Nm)  of 
torque. A tangential force of 14 to28ft.-lbs(62.3 to 124.5N) 
delivered through a6”(150mm) handle will deliver adequate 
torque.  Once  torque  level  reach  over  21ft.-lbs(28.6Nm) 
it  may  distort  the  orifice  seal,  resulting  in  leakage.  For  
exposed piping systems, the sprinkler should be oriented 
so the frame arms are parallel with the branch line pipe.

CAUTION

Do not over-tighten or under-tighten the sprinkler to 

 

compensate for inaccurate escutcheon plate adjustment.

Protection clips are used to protect its bulb. Please have 
clip on at all times during transportation.

MAINTENANCE

Sprinklers  must  never  be  altered  after  manufacture.  Any 
alteration such as painting and coating will directly harm 
the sprinkler and cause malfunctions. Sprinkler in contact 
with corrosive products should be replaced if they cannot 
be cleaned completely.

Visual  inspections  are  recommended  after  installation.  
After installation, a close-up inspection annually will 

 

suffice.

Inspection  and  maintenance  of  fire  protection  system  is 
the  responsibility  of  the  owner.  It  is  recommended  that  
automatic sprinkler system be inspected and tested 

 

according to local and/or national regulations.