26 Shield T3 60 – 500KVA User Manual
前
(c)
Supporting structure of
150kVA, 200kVA, 250kVA and 300kVA
(Bottom view, unit: mm)
前
(d)
Supporting structure of
400kVA and 500kVA
(Bottom view, unit: mm)
Figure2-6
Supporting structure
The steps to position the cabinet are as follows
:
1)
Ensure the supporting structure is in good condition and the mounting floor is
smooth and strong.
2)
Retract the anchor bolts by turning them counter clock wise using wrench. The
cabinet is then supported by the four wheels.
3)
Adjust the cabinet to the right position by the supporting wheels.
4)
Put down the anchor bolts by turning them clock wise using wrench, the cabinet is
then supported by the four anchor bolts.
5)
Ensure the four anchor bolts are in the same height and the cabinet is fixed and
immovable.