32 Shield T3 60 – 500KVA User Manual
150kVA
200kVA
Mains input
Cables crimped OT
terminal
M10
15Nm
Bypass Input
Cables crimped OT
terminal
M10
15Nm
Battery Input
Cables crimped OT
terminal
M10
15Nm
Output
Cables crimped OT
terminal
M10
15Nm
PE
Cables crimped OT
terminal
M10
15Nm
250kVA
300kVA
Mains input
Cables crimped OT
terminal
M12
28Nm
Bypass Input
Cables crimped OT
terminal
M12
28Nm
Battery Input
Cables crimped OT
terminal
M12
28Nm
Output
Cables crimped OT
terminal
M12
28Nm
PE
Cables crimped OT
terminal
M12
28Nm
400kVA
500kVA
Mains input
Cables crimped OT
terminal
M16
96Nm
Bypass Input
Cables crimped OT
terminal
M16
96Nm
Battery Input
Cables crimped OT
terminal
M16
96Nm
Output
Cables crimped OT
terminal
M16
96Nm
PE
Cables crimped OT
terminal
M16
96Nm
2.6.3
Circuit Breaker
The circuit breakers (CB) for the system are recommended in
Table 2-4 Recommended CB
Installed
position
60kVA
80kVA
90kVA
100kVA
120kVA
150kVA
Main input CB
125A/3P
160A/3P
160A/3P
250A/3P
250A/3P
320A/3P
Bypass input
CB
125A/3P
160A/3P
160A/3P
250A/3P
250A/3P
320A/3P
Output CB
125A/3P
160A/3P
160A/3P
250A/3P
250A/3P
320A/3P
Manual
Bypass CB
125A/3P
160A/3P
160A/3P
250A/3P
250A/3P
320A/3P
Battery CB
160A,
250Vdc
225A,
250Vdc
225A,
250Vdc
250A,
250Vdc
400A,
250Vdc
400A,
250Vdc
Installed
position
200kVA
250kVA
300kVA
400kVA
500kVA
Main input CB
400A/3P
630A/3P
630A/3P
800A/3P
800A/3P
Bypass input
400A/3P
630A/3P
630A/3P
800A/3P
800A/3P