52 Shield T3 60 – 500KVA User Manual
Submenu Name
Contents
Meaning
RATE
Configure the rated
Parameter
For the factory use
CONFIGURE
Configure the system
For the factory use
o
Note
Users have various permissions to the configuration of the Setting :( a) for the Date &Time,
LANGUAGE and COMM, user can set on their own without password. (b)For the USER, a one-level
password is needed and the setting must be done by commissioning engineer (c) For the Battery
and SERVICE, a Two-level password is needed and it is set by the after-service personal. (d)For the
RATE and CONFIGURE, a Three-level password is needed and it is set only by the factory.
The “C” stands for Ampere number. For instance, if the battery is 100AH
,
then C=100A.
Warning
Ensure the number of the battery, set via the menu or the monitoring software, is
completely equal to the real installed number. Otherwise it will cause serious damage
to the batteries or the equipment.
3.2.4
Log
Touch the icon
, (At the bottom of the screen), and the system enters the
interface of the Log, as it is shown in
Log menu.The log is listed in reverse
chronological order (i.e. the first on the screen with #1 is the most new), which displays
the events ,warnings and faults information and the data and time they occur and
disappear.
2014
2 14
2014
2 14
2014
2 14
2014
2 14
2014
2
2014
2 14
2014
2
2014
2
14
14
14
2014
2 14
2014
2 14
29
Load On UPS-Set
Module-Exit-Set
Byp Freq Over Track-Set
Load On Bypass-Set
Bypass Volt Abnormal-Set
Load On Bypass-Set
No Load-Set
Load On Bypass-Set
Byp Freq Over Track-Set
Module Inserted-Set
0
4
0
0
0
0
0
4
0
4
1
2
3
5
6
7
4
8
9
10
16 26 1
16 24 27
16 22 31
16 21 33
16 21 33
16 19 41
16 18 45
16 18 45
16 18 45
16 26 1
Figure3-9
Log menu
The follow Table 3-7 gives the complete list of all the UPS events displayed by history
record window and current record window.