Shield T3 60 – 500KVA User Manual
73
changes done on the batteries.
The battery configure ration can be done through the LCD control panel (
) or
though monitoring software (
Figure5-1 Configuration through LCD control panel
Figure5-2 Configuration through monitoring software
5.4.1
Setting of Battery Type
The battery type can be only set through the monitoring software. The system at
present supports lead acid battery and Lithium iron phosphate battery (LFPB).
5.4.2
Setting of Battery Number
1) Setting battery number for Lead- Acid battery
The nominal voltage of one block battery is 12V and for each block of battery, it
consists of 6 cells (each cell of 2V).For the setting, as is shown in Figure5-1, if the
battery is 40, it means that there are 40 blocks of batteries and both the positive and
negative are 20 blocks of batteries.
In the case of cell battery of 2V (usually with large capacity) is used, battery number
should be the same as the block battery. The cell battery actually in use should be 240
cells (6*40), with both and positive and negative of 120 cells.
The battery number setting range is 36-44