22 Shield T3 60 – 500KVA User Manual
(f) Dimensions
of 400KVA and 500kVA (unit: mm)
Figure2-2 Dimensions
Ensure that the floor or installation support can bear the weight of the UPS, batteries,
and battery racks. The weight of batteries and battery racks depends on the site
requirements. The weight for the UPS cabinet is shown in Table 2-1.
Table 2-1 weight for the UPS
Capacity
Weight
60KVA
170Kg
80KVA
210Kg
90KVA
231Kg
100KVA
210Kg
120KVA
266Kg
150KVA
305 Kg
200KVA
350 Kg
250KVA
445 Kg
300KVA
490 Kg
400KVA
810 Kg
500KVA
900 Kg