30 Shield T3 60 – 500KVA User Manual
2.6
Power Cables
2.6.1
Specifications
The UPS power cablesare recommended in
Table 2-2
Recommended cables for power cables
Contents
60kVA
80kVA
90kVA
100kVA
120kVA
150kVA
200kVA
Main
Input
Main Input Current(A)
96
128
144
159
191
239
319
CableSection
(mm²)
A
25
35
35
50
70
95
120
B
25
35
35
50
70
95
120
C
25
35
35
50
70
95
120
N
25
35
35
50
70
95
120
Main
Output
Main Output Current(A)
91
121
136
152
182
227
303
CableSection
(mm²)
A
25
35
35
50
70
70
120
B
25
35
35
50
70
70
120
C
25
35
35
50
70
70
120
N
25
35
35
50
70
70
120
Bypass
Input
(Optional)
Bypass Input Current(A)
91
121
136
152
182
227
303
CableSection
(mm²)
A
25
35
35
50
70
70
120
B
25
35
35
50
70
70
120
C
25
35
35
50
70
70
120
N
25
35
35
50
70
70
120
Battery
Input
Battery Input current(A)
125
167
188
208
250
313
417
CableSection
(mm²)
+
35
50
70
70
95
120
185
-
35
50
70
70
95
120
185
N
35
50
70
70
95
120
185
PE
CableSection
(mm²)
PE
50
50
70
70
95
120
185
Contents
250kVA
300kVA
400kVA
500kVA
Main
Input
Main Input Current(A)
398
478
638
797
CableSection
(mm²)
A
185
185
2*150
2*185
B
185
185
2*150
2*185
C
185
185
2*150
2*185
N
185
185
2*150
2*185
Main
Output
Main Output Current(A)
379
454
606
758
CableSection
(mm²)
A
185
185
2*150
2*185
B
185
185
2*150
2*185
C
185
185
2*150
2*185
N
185
185
2*150
2*185
Bypass
Input
(Optional)
Bypass Input Current(A)
379
454
606
758
CableSection
(mm²)
A
185
185
2*150
2*185
B
185
185
2*150
2*185
C
185
185
2*150
2*185
N
185
185
2*150
2*185
Battery
Input
Battery Input current(A)
521
626
833
1042
CableSection
(mm²)
+
240
240
2*185
2*240
-
240
240
2*185
2*240
N
240
240
2*185
2*240
PE
CableSection
(mm²)
PE
2*120
2*120
2*150
2*150