76 Shield T3 60 – 500KVA User Manual
Figure5-4
Enable the Auto maintenance Discharge period
The EOD voltage of Auto maintenance Discharge is 1.05 times of the normal EOD
voltage.
5.4.11
Warnings for Battery and Environment Temperature Overheat
This function can be set through the monitoring software. The system will read the
temperature information of the battery and environment and give warning of
overheat.
The set range is 25-70
℃
.
The temperature sensor should be placed through the Dry Contact.
5.5
Replacing Dust Filter (optional)
T
here are 3~4 dust filters on the back of UPS’ front door, each filter is held
in place by a bracket on either side of each filter. The procedure of replacing
each filter is as follows:
1.
Open the front door and locate the filters on the back side of the front
door.
2.
Remove one bracket.
3.
Remove the dust filter to be replaced and insert the clean one.
4.
Reinstall the bracket.