Shield T3 60 – 500KVA User Manual
77
6
Product Specification
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics.
6.1
Applicable Standards
The UPS has been designed to conform to the following European and international
standards:
Table 6-1
Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS
used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2
(
C3
)
Method of specifying the
performance and test requirements
of UPS
EN50091-3/IEC62040-3/AS 62040-3
(
VFI
SS 111
)
o
Note
The above mentioned product standards incorporate relevant compliance clauses with
generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission
and immunity (IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and
60950).
6.2
Environmental Characteristics
Table 6-2
Environmental Characteristics
Item
Unit
Requirements
Acoustic noise level
at 1 meter
dB
65dB @ 100% load, 62dB @ 45% load
Altitude of
Operation
m
≤1000,load derated 1% per 100mfrom1000m
and 2000m
Relative Humidity
%
RH
0-95, non-condensing
Operating
Temperature
℃
0-40,Battery life is halved for every 10°C increase
above 20°C
UPS Storage
Temperature
℃
-40-70
Recommended battery
storage temperature
℃
-20
~
30