Parameter Description
Parameters
100
<Setting>
4mA
20mA
Se
tt
in
g
fr
eq
ue
n
P.39
Input current signal
across terminal 4-5
P.501 = 1, frequency
command is selected
P.17 = 0
0V
5V
Se
tt
in
g
fr
eq
ue
nc
y
P.39
Input voltage signal
across terminal 4-5
0V
10V
P.501 = 1 frequency
command is selected
P.17 = 1,2
Note: 1. In “external mode”, “combined mode 2" or “combined mode 4”, if AU is “on” and P.501=1, target
frequency of the inverter will be set by the input signal across terminal 4-5. If AU is “off”, please
refer to P.500~P.502.
2. In “external mode”, “combined mode 2” or “combined mode 4”, if AU and either one of RH, RM,
RL and REX are valid concurrently, multi-speed has higher priority.
3. RL, RM, RH, REX, AU, RT and RUN mentioned at the end of this section are the function names
of “multi-function control terminal”. For the options and functions of multi-function control
terminals, please refer to P.80~P.84, P.86, P.126, P.550. For related wiring, please refer to Section
4. When P.17=0, the toggle switch SW2 on the control board is set to 4~20mA;
When P.17=1 or 2, the toggle switch SW2 on the control board is set to 0~10V.
5. The selection of the range of signal sampling across terminal 4-5 by parameter P.17 will affect
the
parameters value of 4-5 terminal input signal in section 5.
61
.