Parameter Description
Parameters
102
5.23Multi-function Output (P.40, P.85, P.120, P.129, P.130)
P.40 “Multi-function output terminal SO1-SE function selection”
P.85 “Function selection for multi-function relay A1-B1-C1”
P.120 “Output signal delay time”
P.129 “Function selection for multi-function output terminal SO2-SE”
P.130 “Function selection for multi-function relay A2-B2-C2”
Parame
ter
Factory
setting
Setting
range
Remarks
40
1
0~10,
16~19
0
RUN (Inverter running): Signals will be sent out when the output
frequency is equal to or higher than the starting frequency.
1
SU (Reaching the output frequency): Signals will be sent out once
the output frequency reaches the set frequency.
2
FU (Output frequency detection): It is the output signal when
detecting the frequency exceeding the assigned frequency during
the operation.
85
5
3
OL (Overload detection): It is the output signal when the current limit
function is triggered.
4
OMD (Zero current detection): If the current output percentage of
the inverter is less than the set value of P.62 and has exceeded P.63
for a period of time, OMD will output the signal.
5
ALARM (Alarm detection): An alarm signal detected.
129
2
6
PO1 (Section detection): In the programmed operation mode, the
signal will be sent out at the end of each frequency operation.
7
PO2 (Periodical detection): In the programmed operation mode, the
signal will be sent out at the end of each operation cycle.
8
PO3 (Pause detection): In the programmed operation mode, the
signal will be sent out when the operation is suspended.
130
0
9
BP (Inverter output): Switch between the inverter operation and the
commercial power-supply operation function; in inverter operation,
BP will send out signals.
10
GP (Commercial power-supply output): Switch between the inverter
operation and the commercial power-supply operation function; in
the commercial power-supply operation, GP will send out signals.
16
FAN (Abnormal signal of fan): the output signal when the fan
detection return circuit has a problem.
17
RY (The accomplishment of inverter running preparation): the output
signal when resetting is accomplished after the inverter is powered
on. (the starting signal ON is in the started state)
18
Maintenance alarm detection
19
OL2(Over torque alarm output): refer to P.260 instruction