Parameter Description
Parameters
115
Parameter
Factory
setting
Setting
range
Remarks
65
0
0~4
0
When P.65=0, retry is invalid. When alarm occurs, the
voltage output is stopped, and all the inverter functions
are disabled.
1
When P.65=1, in case of “over-voltage b/P
and -/N”, the voltage output is stopped. After a period
of waiting time (the set value of P.68), the inverter will
perform the retry function.
2
When P.65=2 and “over-current” occurs, voltage
output is stopped. After a period of waiting time (the
set value of P.68), the inverter will perform the retry.
3
When P.65=3, in case of “over-voltage b/P
and -/N”, the voltage output is stopped. After a period
of waiting time (the set value of P.68), the inverter will
perform the retry.
4
When P.65=4, all the alarms have the retry function.
When the alarm goes off, the voltage output will be
stopped. After a period of waiting time (the set value
of P.68), the inverter will perform the retry.
67
0
0~10
0
When P.67=0, retry is invalid.
1~
10
When P.67≠0, given continuous alarm occurs for times
within the set value of P.67, the inverter will perform
the retry function. However, once the set value of P.67
is exceeded, the inverter will not perform the retry
function.
68
1s
0~360s
---
<Setting>
• For each time a retry happens, the value of P.69 will be increased by one automatically.
Therefore, the number of P.69 read from the memory indicates the number of retries that
have occurred.
• If P.69 is rewritten with 0, the number of retry executed is cleared.
Note: The inverter will perform retry only after the retry waiting time of P.68.Therefore when using this
function, please be aware of the possible danger when operating the inverter.