Parameter Description
Parameters
159
• When P.245=1 or 11, turning on the power will turn on the fan. When the power is turned off,
the fan will be off, too.
• When P.245=2 or 12, the fan will be turned on if the temperature of the heat sink is higher
than 40
℃
. When the power is turned off, the fan will be turned off, too.
• When P.245=3 or 13, the fan will be turned on when the temperature of the heat sink is
higher than 60
℃
. When the temperature of the heat sink is lower than 40
℃
, the fan will be
turned off.
Note: please refer to the parameter P.40, P.85, P.129, P.130.
5.6
7
Modulation Coefficient (P.246)
P.246 "Modulation coefficient”
Parameter
Factory setting
Setting range
Remarks
246
1
0.90~1.20
---
<Setting>
• P.246 is used to determine the ratio between the maximum output voltage and the input
voltage. The users can use this parameter to obtain an output voltage that is higher than
the input voltage. But the output voltage waveform at this point will generate distortion and
contain assorted harmonics. It may also increase the motor torque harmonics and noises.
5.6
8
Commercial Power Supply Frequency Operation Function
(P.247~P.250)
P.247 “MC switchover interlock time”
P.248 “Start waiting time”
P.249 “Automatic switchover frequency from inverter to commercial power
supply frequency”
P.250 “Automatic switchover frequency range from commercial power supply to
inverter”
Parameter
Factory setting
Setting range
Remarks
247
1s
0.1~100s
---
248
0.5 s
0.1~100 s
---
249
99999
0~60Hz, 99999
---
250
99999
0~10Hz, 99999
---