3.7.2 Power cable specification / pressing connection terminal specification
Inverter type
Power cable specification
Pressing connection
terminal
specification (used
by power cables)
Power supply terminal
(R/L1.S/L2.T/L3)
Loading terminal
(U/T1.V/T2.W/T3)
Cables
for
power
supply
(R/L1.
S/L2.T/
L3)
Cables for
loading
(U/T1.V/T2
.W/T3)
Crimping
terminal
(mm
2
)
Tightening
torque
(Kgf.cm)
Crimping
terminal
(mm
2
)
Tightening
torque
(Kgf.cm)
SF-040-1.5K-GT
2.5
12.2
2.5
12.2
2-3.5
2-3.5
SF-040-2.2K-GT
2.5
18
2.5
18
2-4
2-4
SF-040-3.7K-GT
2.5
18
2.5
18
2-4
2-4
SF-040-5.5K-GT
3.5
30
2
18
3.5 - 5
2 - 5
SF-040-7.5K-GT
3.5
30
3.5
30
3.5 - 5
3.5 - 5
SF-040-11K-GT
5.5
30
5.5
30
5.5 - 5
5.5 - 5
SF-040-15K-GT
14
30
8
30
14 - 6
8 - 6
SF-040-18.5K-GT
14
30
8
30
14 - 6
8 - 6
SF-040-22K-GTS
22
30
14
30
22 - 6
14 - 6
SF-040-22K-GT
22
30
14
30
22 - 8
14 - 8
SF-040-30K-GT
22
30
22
30
22 - 8
22 - 8
SF-040-37K-GT
22
30
22
30
22 - 8
22 - 8
SF-040-45K-GT
38
30
38
30
38 - 10
38 -10
SF-040-55K-GT
60
200
60
200
60 - 10
60 - 10
SF-040-75K-GT
60
200
60
200
60 - 10
60 - 10
SF-040-90K-GT
60
200
60
200
60 - 10
60 - 10
SF-040-110K-GT
80
200
80
200
80 - 10
80 - 10
SF-040-132K-GT
125
300
125
300
125-10
125 - 10
SF-040-160K-GT
150
250
150
250
150-12
150-12
SF-040-185K-GT
2×100
250
2×100
250
100-12
100-12
SF-040-220K-GT
2×100
250
2×100
250
100-12
100-12