Primary Operation
Primary operation
49
4.2.5 Basic operation procedures for combined mode 1 (P.79=4)
Step
Description
1
In Combined Mode 1, indicating lamp
and
will light up.
Note: For selecting and switching the operation mode, please refer to Section 4.1.
2
Enter the frequency setting mode and enter the target frequency into memory.
Note: For detailed frequency setting procedures, please refer to Section 4.1.4.
3
Set the target frequency via DU01 operation panel and start the inverter by the external terminals.
At this point, indicating lamp
or
will light up, indicating that the motor is
running.
Note: For detailed operation flow for the monitoring mode, please refer to Section 4.1.4.
4
When the external terminals stop the output signals, the motor will decelerate until it comes to a
full stop.
Indicating lamp
or
will not turn off until the inverter stops the output.
4.2.6 Basic operation procedures for combined mode 2 (P.79=5)
Step
Description
1
In Combined Mode 2, indicating lamp
and
will light up.
Note: For selecting and switching the operation mode, please refer to Section 4.1.
2
The target frequency is set by the external terminals (the default priority is from high to low):
If the target frequency is set by multi-speed stage levels, please refer to P.4 in Chapter 5.
If the target frequency is set by the input signal of terminal A2/B2 on PG03 (switching SW11 to DI
in the meantime), please refer to P.356 in Chapter 5.
If the target frequency is set by PWM input pulse (switching SW11 to HDI in the meantime), please
refer to P.550 on Chapter 5.
If the target frequency is set by the input signal across terminal 2-5, please refer to P.38 in Chapter
5.
If the target frequency is set by the input signal across terminal 4-5, please refer to P.39 in Chapter
5.
If the target frequency is set by the input signal across terminal 1-5, please refer to P.509 in
Chapter 5.
If the target frequency is set by the high-speed pulse input across terminal HDI (switching SW11 to
HDI in the meantime), please refer to P.522 on Chapter 5.
3
Press
FWD
or
REV
of DU01 operation panel to run the motor. At this point, indicating
lamp
or
will light up, indicating that the motor is running.
Note: 1. For detailed operation flow for the monitoring mode, please refer to Section 4.1.4.
2. While the motor is running, the user can enter the frequency setting mode to change the
target frequency for regulating the motor speed.
4
Press
STOP
STOP
RESET
RESET
and the motor will begin to decelerate until it comes to a full stop.
Indicating lamp
or
will not turn off until the inverter stops the output.