Parameter Description
Parameters
57
5.2 The Rage of the Output Frequency (P.1, P.2 and P.18)
P.1 “Maximum frequency”
P.2 “Minimum frequency”
P.18 “High-speed maximum
frequency”
Related parameters
P.13
“
Starting frequency
”
● The upper and lower limits of the output frequency can be restricted.
Parameter
Factory setting
Setting range
Remarks
1
120Hz(55kW or below)
0~120Hz
---
60Hz(75kW or above)
2
0Hz
0~120Hz
---
18
120Hz
120~650Hz
---
P.1(P.18)
P.2
Output
frequency
(
Hz
)
Setting frequency(Hz
)
<Setting>
• If the target frequency
≦
P
.2, the steady output frequency equals to P.2.
• If P.2<target frequency
≦
P.1 (P.18), the steady output frequency equals target frequency.
• If P.1 (P.18)
<
target frequency, the steady output frequency equals P.1.
Note: 1. The “maximum frequency" and the “high-speed maximum frequency” are interrelated. If the target
upper limit frequency is set below 120Hz, use P.1 as the maximum frequency (the setting range
of P.1 is 0~120 Hz). If the target frequency limited to between 120~650 Hz, use P.18 as the
maximum frequency (the setting range of P.18 is 120~650 Hz).
2. If P.1<P.2, the steady output frequency will be clamped to P.1.
3. The set frequency value cannot exceed the value of P.1.