Parameter Description
Parameters
64
5.8 Starting Frequency (P.13)
P.13 “Starting frequency”
Related parameters
P.2
“
Minimum frequency
”
● When the motor starts up, the instantaneous output frequency of the inverter is called
“starting frequency”.
Parameter
Factory setting
Setting range
Remarks
13
0.5Hz
0~60Hz
---
<Setting>
• If the target frequency of the inverter is lower than the setting value of P.13, the motor will
not run. When the signal of the motor starts, the output frequency will go up from the value
of P.13.
Time
Output
frequency
(
Hz
)
P.13
Startup signal
input
5.9 Load Pattern Selection (P.14, P.98~P.99, P.162~P.169)
P.14 “Load pattern selection”
P.98 “Middle frequency 1”
P.99 “Output voltage 1 of
middle frequency”
P.162 “Middle frequency 2”
P.163 “Output voltage 2 of
middle frequency”
P.164 “Middle frequency 3”
P.165 “Output voltage 3 of
middle frequency”
P.166 “Middle frequency 4”
P.167 “Output voltage 4 of
middle frequency”
P.168 “Middle frequency 5”
P.169 “Output voltage 5 of
middle frequency”
Related parameters
P. 46
“
The second torque boost
”
P. 80~P. 84 , P. 86, P.126, P.550
“
Multi-function terminals selection
”
P. 0
“
Torque boost
”