Parameter Description
Parameters
65
Parameter
Factory setting
Setting range
Remarks
14
0
0~13
P.14=4~13 are different VF curve
options.
98
3Hz
0~650Hz
---
99
10%
0~100%
---
162
99999
0~650Hz, 99999
---
163
0%
0~100%
---
164
99999
0~650Hz, 99999
---
165
0%
0~100%
---
166
99999
0~650Hz, 99999
---
167
0%
0~100%
---
168
99999
0~650Hz, 99999
---
169
0%
0~100%
---
<Setting>
• If P.14=4, suppose that P.19=220V, P.98=5Hz and P.99=10%, when the inverter is running
at 5Hz, the output voltage equals P.19×P.99
=
220V×10%
=
22V.
• If RT is “on”, P.46
“The Second Torque Boost” is valid.
P.14=0
Output frequency
P.0
0
P.3
Output voltage
P.19
Applicable to constant torque loads
(convey belt, etc.,)
P.14=1
P.0
0
P.3
P.19
Output voltage
Output frequency
Applicable to variable torque loads
(Fans and pumps, etc.)
P.14=2
P.0
0
P.3
P.19
Forward rotating
Reversely rotating
Output voltage
Output frequency
Ascending / descending loads
P.14=3
P.0
0
P.3
P.19
Forward rotating
Reversely rotating
Output voltage
Output frequency
Ascending / descending loads