Parameter Description
Parameters
75
●
When the communication parameters are revised, please reset the inverter. The SF-GT
inverters have two communication protocols for selection, namely, Shihlin protocol and
Modbus protocol. Parameter P.32, P.36, P.52, P.55 and P.153 are suitable for both
protocols. P.48~P.51 is only suitable for the Shihlin protocol, while P.154 is only suitable for
the Modbus protocol. Please refer to communication protocols for more details.
Parameter
Factory
setting
Setting range
Remarks
32
1
0, 1, 2,3
0
Baud rate: 4800bps
1
Baud rate: 9600bps
2
Baud rate: 19200bps
3
Reserved
33
1
0, 1
0
Modbus protocol
1
Shihlin protocol
36
0
0~254
(Note 1)
48
0
0, 1
0
Data length: 8 bit
1
Data length: 7 bit
49
0
0, 1
0
Stop bit length: 1 bit
1
Stop bit length: 2 bit
50
0
0, 1, 2
0
No parity verification
1
Odd
2
Even
51
1
1, 2
1
CR only
2
Both CR and LF
52
1
0~10
(Note 2)
53
99999
0~999.8s, 99999
0~999.8
Use the set value for the
communication overtime test
99999
99999: No communication overtime
test (Note 3)
153
0
0, 1
0
Warn and call to stop
1
No warning and keep running
154
4
0~5
0
Protocol, 1, 7, N and 2 (Modbus,
ASCII) (Note 4)
1
1
、
7
、
E
、
1 (Modbus, ASCII)
2
1
、
7
、
O
、
1 (Modbus, ASCII)
3
1
、
8
、
N
、
2 (Modbus, RTU)
4
1
、
8
、
E
、
1 (Modbus, RTU)
5
1
、
8
、
O
、
1 (Modbus, RTU)