Parameter Description
Parameters
92
Item
Shihlin
protocol
Reference
code
Modbus
Reference
code
Modbus
address
Data content and function description
M
on
ito
ring
Frequency
setup
EEPROM
H73
H03
H1009
H0000~HFDE8(Two decimal points
when P.37=0; One decimal point
when non-zero.)
RAM
H6D
H1002
Output frequency
H6F
H1003
H0000~H9C40(Same as above)
Output current
H70
H1004
H0000~HFFFF(two decimal points)
Output voltage
H71
H1005
H0000~HFFFF(two decimal points)
Abnormal content
H74
H1007
H0000~HFFFF
:
Abnormal codes
from the last two times
H0000~HFFFF:
H74: Error code 1 and 2
b15 b8 b7 b0
Error code 2
Error code 1
H75: Error code 3 and 4
b15 b8 b7 b0
Error code 4
Error code 3
For abnormal codes, please refer to
the abnormal code list in the
abnormal record parameter
H75
H1008
Operation reference write-in
HFA
H06/
H10
H1001
H0000~HFFFF
b8~b15
:
Preservation
b7
:
Inverter emergency stop(MRS)
b6
:
The second function (RT)
b5
:
High speed (RH)
b4
:
Medium speed (RM)
b3
:
Low speed (RL)
b2
:
Reverse rotation (STR)
b1
:
Forward rotation (STF)
b0
:
Preservation
Inverter reset
HFD
H06/
H10
H1101
H9696
:
P.997 function
When communicating with the
position machine, resetting the
inverter will cause the inverter to be
incapable of sending data back to the
position machine.
Parameter delete
HFC
H06/
H10
H1104
H5A5A
For details, please refer to
the parameter restoration
status table.
H1103
H9966
H1106
H9696
H1105
H55AA
H1102
HA5A5