5.19 Function Selection of HDI Terminal and Analog Terminal (P.500,
P.501, P.502, P.503)
P.500 “Function selection of terminal 2-5”
P.501 “Function selection of terminal 4-5”
P.502 “Function selection of terminal 1-5”
P.503 “Function selection of terminal HDI”
<Setting>
•
When frequency reference is selected, 0
~
±10V/4~20mA corresponds to 0~the maximum
output frequency setting.
Note: 1. The default priority level of terminal function selection is 2-5 > 4-5 > 1-5 > HDI, so if you want to
set the terminal 1-5 as frequency reference, P.500 and P.501 should be set at 0 and P.502 should
be set at 1.
2. The function selection of terminal HDI (P.503) is only valid in the mode of tension.
Parameter
Factory setting
Setting range
Remarks
500
1
0~10
0
:
non-function
1
:
frequency reference
2
:
Torque reference
3
:
PID target value
4
:
PID feedback signal
5
:
target tension setting
6
:
line speed setting
7
:
feedback line speed
8
:
real-time curling radius
9
:
initial curling radius
10
:
material thickness
501
1
502
0
503
0