Parameter Description
Parameters
129
Parameter
Factory
setting
Setting
range
Remarks
89
0
0~10
0
Slip compensation is forbidden.
10
The compensation value is 3% of the target
frequency when P.89 = 10.
5.43 The Inverter Model (P.90)
P.90 “The inverter model”
● P.90 is used to show the type and capacity of inverter, and the parameter can only be read.
P.90 =
Input voltage: 1: 220V 1-PHASE
2: 220V 3-PHASE
3: 440V 3-PHASE
Applicable motor capacity: please
refer to the following table
The applicable motor capacity is as following table:
Value (value of the two
low-order bits of P.90)
capacity (kw)
Value (value of the two
low-order bits of P.90)
capacity (kw)
4
1.5
14
37
5
2.2
15
45
6
3.7
16
55
7
5.5
17
75
8
7.5
18
90
9
11
19
110
10
15
20
132
11
18.5
21
160
12
22
22
185
13
30
23
220
5.44 Frequency Jump (P.91~P.96)
P.91~P.96 “Frequency jump”
● To avoid system’s mechanical resonance frequency when running the motor, the inverter
provides three sets of jump frequencies, namely, P.91 (the first set), P.92 (the second set),