Parameter Description
Parameters
146
5.57 SF-GT Types Selection (P.186)
P.186 “SF-GT Types Selection”
Parameter Factory setting
Setting range
Remarks
186
1
0~1
0
Normal Duty(ND)
,
apply to the fans and
water pump type duty.
1
Heavy Duty(HD)
,
apply to other duties
,
such as
:
constant
torque type.
<Setting>
For example: If setting Normal Duty, execute the following steps:
1. Set P.186=0;
2. Execute P.998 to return to the default value.
3. Execute the reset function of P.997.
If setting Normal Duty, execute the following steps:
1. Set P.186=1;
2. Execute P.998 to return to the default value.
3. Execute the reset function of P.997.
5.5
8
Firmware version and expansion board message (P.124, P.188)
P.124 “Expansion board version”
P.188 “Firmware version”
● It is used to display the current Firmware version or type of the inverter/expansion board
which is readable only.
5.5
9
Factory Setting Function (P.189)
P.189 “Factory setting function”
Parameter Factory setting
Setting range
Remarks
189
1
0, 1
0
The default value of frequency-related
parameter belongs to the 60Hz system.
1
The default value of frequency-related
parameter belongs to the 50Hz system.
● According to different power frequency and the default motor frequency, the user can
select frequency related parameters. The default value is either 50Hz or 60Hz. Description
on relevant parameters are presented in the table below: