Parameter Description
Parameters
171
does not permit auto-tuning, set P.301 to 2 (static measurement) if motoring is running.
3. Sensorless vector control: Auto-tuning function can be used to enhance the control function.
Before setting P.300 to 3 or 4, first set the motor parameters or the auto-tuning function to
improve the control accuracy.
4. When P.300=1 and the mode of Close-loop V/F control (VF + PG) is selected, please make sure
that the motor poles P.303 is correct.
5.7
8
Motor Parameter (P.302~P.312)
P.302 “Motor rated power”
P.303 “Motor poles”
P.304 “Motor rated voltage”
P.305 “Motor rated frequency”
P.306 “Motor rated current”
P.307 “Motor rated rotation speed”
P.308 “Motor excitation current”
P.309 “Stator resistance”
P.310 “Rotor resistance”
P.311 “Leakage inductance”
P.312 “Mutual inductance”
Parameter
Factory setting
Setting range
Remarks
302
0
0~160
---
303
4
0~8
---
304
220/380V
0~440V
P.189=1
220/440V
P.189=0
305
50Hz
0~650Hz
60Hz
P.189=0
306
Horsepower-based
0~500A
---
307
1410 r/min
0~65535 r/min
P.189=1
1710 r/min
P.189=0
308
Horsepower-based
0~500A
---
309
Horsepower-based
0~65535mΩ
---
310
Horsepower-based
0~65535mΩ
---
311
Horsepower-based
0~6553.5mH
---
312
Horsepower-based
0~6553.5mH
---
<Setting>
• When the motor can be fully separated from the load, select P.301=1. When the motor is
running, the motor parameter will carry out auto-tuning. Then press
FWD
or
REV
on the keyboard
panel for the inverter to automatically calculate the following parameter: P.308~P.312.
• When the motor cannot be fully separated from the load, select P.301=2. When the motor is