107
4. Parameter description
Parameter
4.53 Multimachine constant pressure system function
(
P.200
,
P.209
,
P.210
,
P.213~P.217
,
P.223~P.225
)
P.200
“
Constant pressure system
function selection
”
P.209
“
Upper limiter duration time
”
P.210
“
Lower limiter duration time
”
P.213
“
Full-voltage starting acceleration time
”
P.214
“
Full-voltage starting deceleration time
”
P.215
“
Maximum frequency
”
P.216
“
Minimum frequency
”
P.217
“
Motor switching allowable deviation
”
P.223
“
Analog feedback bias pressure
”
P.224
“
Analog feedback gainpressure
”
P.225
“
pressure command
(
Given by the keyboard panel
)”
Parameter
Factory setting
Setting range
Remarks
200
0
0~14
---
209
5.0min
0.1~10.0min
---
210
5.0min
0.1~10.0min
---
213
5.00s
0.01~20.00s/0.1~200.0s
214
5.00s
0.01~20.00s/0.1~200.0s
If P.21=0, minimum increments of
P.213 and P.214 is 0.01 seconds.
If P.21=1, minimum increments of
P.213 and P.214 is 0.1 seconds.
215
50.00Hz
20.00~60.00Hz
---
216
20.00Hz
0~20.00Hz
---
217
0
0%~20.0%
---
223
0%
0~100.0%
---
224
100%
0~100.0%
---
225
20%
0~100.0%
---
PDF created with pdfFactory trial version