128
Appendix 1 Parameter list
Parameter list
Parameter
number
Name
Setting range
Minimum
setting
unit
Default value
User
setting
value
Reference
page
P.44
Second acceleration time
0~360.00s/
0~3600.0s
、
99999
0.01s/0.1s
99999
P50
P.45
Second deceleration time
0~360.00s/
0~3600.0s
、
99999
0.01s/0.1s
99999
P50
P.46
Second torque boost
0~30%, 99999
0.1%
99999
P46
P.47
Second base frequency
0~400Hz, 99999
0.01Hz
99999
P48
P.48
Data length
0, 1
1
0
P62
P.49
Stop bit length
0, 1
1
0
P62
P.50
Parity check selection
0, 1, 2
1
0
P62
P.51
CR and LF selection
1, 2
1
1
P62
P.52
Number of communication
reties
0~10
1
1
P62
P.53
Communication check time
interval
0~999.8s, 99999
0.1s
99999
P62
P.54
AM
terminal
function
selection
0, 1
1
0
P74
P.55
Frequency
monitoring
reference
0~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P74
P.56
Current monitoring reference
0~500A
0.01A
Related output
current
P74
P.57
Retry coasting time
0~30s, 99999
0.1s
99999
P77
P.58
Retry voltage rising time
0~60s
0.1s
5s
P77
P.59
Reserved
P.60
Input signal filtering constant
0~31
1
31
P78
P.61
Remote control function
0~3
1
0
P78
P.62
Zero current detection
0~200%, 99999
0.1%
5%
P81
P.63
Zero current detection time
0.05~1s, 99999
0.01s
0.5s
P81
P.64
FM/AM
Output
terminal
selection
0
、
1
1
0
P74
P.65
Retry selection
0, 1, 2, 3
1
0
P82
P.66
Stall prevention operation
reduction starting frequency
0~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P57
P.67
Number of retries at alarm
occurrence
0~10
1
0
P82
P.68
Retry waiting time
0~360s
0.1s
1s
P82
P.69
Retry accumulation times
0
0
0
P82
PDF created with pdfFactory trial version