132
Appendix 1 Parameter list
Parameter list
Parameter
number
Name
Setting range
Minimum
setting
unit
Default value
User
setting
value
Reference
page
P.139 Bias of external input frequency
0.0%~100.0%
0.1%
0.0%
P64
P.140
Gain
of
external
input
frequency
0.1%~200.0%
0.1%
100.0%
P64
P.141
Bias polarity
of voltage signal
and reverse motion of negative
bias
0~11
1
0
P64
P.142 Speed 8
0~400Hz
0.01Hz
0Hz
P49
P.143 Speed 9
0~400Hz, 99999
0.01Hz
99999
P49
P.144 Speed 10
0~400Hz, 99999
0.01Hz
99999
P49
P.145 Speed 11
0~400Hz, 99999
0.01Hz
99999
P49
P.146 Speed 12
0~400Hz, 99999
0.01Hz
99999
P49
P.147 Speed 13
0~400Hz, 99999
0.01Hz
99999
P49
P.148 Speed 14
0~400Hz, 99999
0.01Hz
99999
P49
P.149 Speed 15
0~400Hz, 99999
0.01Hz
99999
P49
P.150 Restart mode selection
0~221
1
0
P77
P.151
Zero-speed
control
function
selection
0, 1
1
0
P97
P.152
Voltage
instruction
when
zero-speed control
0~30%
0.1%
5%
P97
P.153 Communication error handling
0, 1
1
0
P62
P.154 Modbus protocol selection
0~5
1
4
P62
P.155 Over torque detection lelve
0~200%
0.1%
0%
P97
P.156 Over torque detection time
0.1~60s
0.1s
1
P97
P.157
External
terminals
filter
function selection
0~200
1
4
P98
P.158 External terminal power enable
0
、
1
1
0
P98
P.159 energy-saving control function
0
、
1
1
0
P99
P.160
stall prevention operation level
when restart
0~150%
0.1%
100%
P77
P.161 Multi-function display selection
0~6
1
0
P99
P.162 Middle frequency 2
0~400Hz
、
99999
0.01Hz
99999
P54
P.163
Voltage output 2 at middle
frequency
0~100%
0.1
0
P54
P.164 Middle frequency 3
0~400Hz
、
99999
0.01Hz
99999
P54
P.165
Voltage output 3 at middle
frequency
0~100%
0.1
0
P54
PDF created with pdfFactory trial version