29
2.
Introduction of Shihlin Inverter
Introduction of Inverter
2.7.2 Power cable specification/pressing connection terminals specification
Power cable specification
Pressing connection terminal
specification (used by power cables)
Cables for the power
supply R.S.T
Cables for the output
U.V.W
Inverter type
Crimping
terminal
(
mm2
)
Tightening
torque
(
Kgf-cm
)
Crimping
terminal
(
mm2
)
Tightening
torque
(
Kgf-cm
)
Cables for the
power supply
R.S.T (mm
2
)
Cables for the
output U.V.W
(mm
2
)
SF-020-5.5K
5.5
30
5.5
30
5.5 - 4
5.5 - 4
SF-020-7.5K
14
30
8
30
14 - 5
8 - 5
SF-020-11K
14
30
14
30
14 - 5
14 - 5
SF-020-15K
22
30
22
30
22 - 5
22 - 5
SF-020-18.5K
38
30
38
30
38 - 6
38 - 6
SF-020-22K
38
30
38
30
38 - 6
38 - 6
SF-020-30K
60
200
60
200
60 - 8
60 - 8
SF-020-37K
80
200
80
200
80 - 8
80 - 8
SF-020-45K
100
200
100
200
100 - 10
100 - 10
SF-020-55K
100
200
100
200
100 - 10
100 - 10
SF-040-5.5K
3.5
30
2
18
5.5 - 4
2 - 4
SF-040-7.5K
3.5
30
3.5
30
5.5 - 4
5.5 - 4
SF-040-11K
5.5
30
5.5
30
5.5 - 6
5.5 - 6
SF-040-15K
14
30
8
30
14 - 6
8 - 6
SF-040-18.5K
14
30
8
30
14 - 6
8 - 6
SF-040-22K
22
30
14
30
22 - 6
14 - 6
SF-040-30K
22
30
22
30
22 - 6
22 - 6
SF-040-37K
22
30
22
30
22 - 6
22 - 6
SF-040-45K
38
30
38
30
38 - 8
38 - 8
SF-040-55K
60
200
60
200
60 - 8
60 - 8
SF-040-75K
60
200
60
200
60 - 8
60 - 8
SF-040-90K
60
200
60
200
60 - 10
60 - 10
SF-040-110K
80
200
80
200
80 - 10
80 - 10
SF-040-132K
100
200
125
300
100 - 10
100 - 10
SF-040-160K
125
300
125
300
150 - 10
150 - 10
PDF created with pdfFactory trial version