49
4. Parameter description
Parameter
4.4
Multi-speed (P.4~P.6, P.24~P.27, P.142~P.149)
P.4
“
speed 1(high speed)
”
P.5
“
speed 2(medium speed)
”
P.6
“
speed 3 (low speed)
”
P.24~P.27
“
speed 4 to 7
”
P.142~P.149
“
speed 8 to 15
”
Related parameters
P.2
“
Minimum frequency
”
P.1
“
Maximun frequency
”
P.29
“
Acceleration/deceleration
pattern selection
”
P.80~P.84, P.86,P.126~P.128
P.79
“
Operation mode selection
”
“
Multi-function terminals selection
”
Parameter
Factory setting
Setting range
Remarks
4
60Hz
0~400Hz
---
5
30Hz
0~400Hz
---
6
10Hz
0~400Hz
---
24~27
99999
0~400Hz, 99999
99999, is not chosen
142
0Hz
0~400Hz
---
143~149
99999
0~400Hz, 99999
99999, is not chosen
<Setting>
•
If all the setting values of P.24~P.27 and P.142~P.149 are not 99999,
‘
16-speed operation
’
is active.
It means that with the combination of RL, RM, RH and REX, there are 16 kinds of speeds in all.
For the setting of the target frequency of the inverter, please refer to the figure below.