53
4. Parameter description
Parameter
To achieve an optimum control, P.11 and P.12 should be set properly.
As shown as follows:
P.12
Time
P.11
Output
frequency
(
Hz
)
P.10
DC
braking
voltage
Time
Stop signal input
Note: Users must set P.11 and P.12 appropriately in order to obtain the best control characteristics.
4.8
Starting frequency (P.13)
P.13
“
Starting frequency
”
●
When the motor starts up, the instant output frequency of the inverter is called
‘
starting frequency
’
.
Parameter
Factory setting
Setting range
Remarks
13
0.5Hz
0~60Hz
---
<Setting>
•
If the target frequency of the inverter islower than the setting value of P.13, the motor will not run.
When the signal of the motor start, the output frequency will go up begin with the value of P.13.