54
4. Parameter description
Parameter
4.9
Load pattern selection (P.14)
P.14
“
Load pattern selection
”
Parameter
Factory setting
Setting range
Remarks
14
0
0~13
When P.14=5~13, it provides 9 kinds
of different VF curve.
<Setting>
•
If P.14=4, suppose that P.19=220V, P.98=5HZ, P.99=10%, when the inverter is running at 5HZ, the
output voltage equals P.99
×
P.19=10%
×
220V=22V.
•
If RT is
‘
on
’
, P.46
‘
Second Torque Boost
’
is valid.
P.14
=
0
Applicable to Constant torque loads (conveyer belt etc.)
P.14
=
1
Applicable to Variable torque loads (fans and pumps etc.)
PDF created with pdfFactory trial version