73
4. Parameter description
Parameter
Note: In this paragraph, SU is the function name of
‘
multi-function output terminal
’
. Please refer to P.40
、
P.129
、
P.130for function selection and features. About wiring, please refer to section 2-5.
4.22
Output frequency detection (P.42, P.43)
P.42
“
Output frequency detection for
forward rotation
”
P.43
“
Output frequency detection for
reverse rotation
”
Parameter
Factory setting
Setting range
Remarks
42
6Hz
0~400Hz
---
43
99999
0~400Hz, 99999
99999: same as P.42 setting
<Setting>
•
If P.42=30 and P.43=20, then a signal (FU) is output when the forward rotation output frequency
exceeds 30Hz or when the reverse rotation output frequency exceeds 20Hz.
•
If P.42=30 and P.43=99999 (the default value), then a signal (FU) is output when the forward or
reverse rotation output frequency exceeds 30Hz.
PDF created with pdfFactory trial version