78
4. Parameter description
Parameter
4.25
Input signal filter constant (P.60)
P.60
“
Input signal filter constant
”
●
When the running frequency is set by a voltage signal or a current signal, the voltage/current signal
would be processed by an A/D converter. Due to the effect of device accuracy or noises, the
external voltage signal or current signal may fluctuate and thus the running frequency fluctuates.
●
The
‘
Input signal filter constant setting P.60
’
is used to filter the fluctuation of the running
frequency caused by the above factors. The larger the P.60 set value is, the better the filter
performance, but larger delay is resulted in.
Parameter
Factory setting
Setting range
Remarks
60
31
0~31
---
4.26
Remote setting function selection (P.61)
P.61
“
Remote setting function
selection
”
●
If the operation box is located away from the control box, you can use contact signals to perform
continuous variable-speed operation, without using analog signals, when
in
‘
external mode
’
,
‘
combined
mode 1
’
or
‘
combined mode 5
’
.
Remarks
Parameter
Factory
setting
Setting
range
Set
value
Remote set
function
Frequency setting storage function
0
No
---
1
Yes
2
No
61
0
0~3
3
Yes
No
(the remote setting frequency is cleaned
out by STF/STR
‘
turn off
’
)