96
4. Parameter description
Parameter
4.41 Operation panel frequency monitoring selection function (P.110)
P.110
“
Operation panel frequency monitoring selection
”
Parameter
Factory
setting
Setting
range
Remarks
0
When the inverter starts, the operation panel
enters the monitoring mode automatically, and the
screen displays the output frequency.( is 3% of
the target frequency is after slip compensation)
1
When the inverter starts, the screen of the
operation panel displays the target frequency.
110
0
0, 1, 2
2
When the inverter starts, the operation panel
enters the monitoring mode automatically, and the
screen displays the current pressure and feedback
pressure of constant pressure system.
Note: When P.110=2, t
he screen displays shows two sections.
In decimal for disjunctive boundaries, left
is the target pressure, and right is the feedback pressure.
As shown in figure
,
20
means
target pressure is 2.0Kg/cm
2
, 30 means feedback pressure is 3.0Kg/cm
2
.
P.120
→
Please refer to P.40
P.126~P.128
→
Please refer to P.80
P.129~P.130
→
Please refer to P.40
P.139~P.140
→
Please refer to P.38
P.142~P.149
→
Please refer to P.4
P.150
→
Please refer to P.57