98
4. Parameter description
Parameter
Parameter
Factory setting
Setting range
Remarks
0
No detection of over torque
155
0%
0~200%
0.1~200%
When over torque detection,
alarm is display and the motor stop
156
1s
0.1~60s
4.44
External terminal filter function (P.157)
P.157
“
External terminals filter function selection
”
Parameter
Factory setting
Setting range
157
4
0
~
200ms
●
P.157 select response time to the signal of external terminal.
4.45 External terminal power enable function
(
P.158
)
P.158
“
External terminal power enable
”
Parameter
Factory setting
Setting range
158
0
0
~
1
●
If P.158=1
,
select the external terminal power enable function.At this situation, if the
multi-function terminal function is STF, STR, RUN or MPO witch have been set, and opposite
terminal is connected before the power on, the inverter will not run, you should connect the
terminal again, the inverter will start running. If P.158=1 the terminal connected before the power
on, if power on the inverter running
immediately.