15
< Note >
When disconnecting piping from the external tank, turn the lever to the “A” side, and attach the
bundled plug (R1/2”)to the external tank fuel inlet/return.
(2) If using an external fuel tank
Connect hoses from the external fuel tank to the
external fuel inlet and the external fuel return.
Change the lever of the 3way fuel valve to the “B”
side to supply fuel from the external tank.
(Refer to “
9-5. Connecting an External Fuel Tank
”
for corresponding procedures.)
6.
Transporting/Installing
6-1. Transport Procedures
WARNING : INJURY
Do not lift up the unit using tie down. Use of such could result in the generator falling.
No persons should be under a lifted generator.
CAUTION : INJURY
Always be sure to use lifting hooks when lifting up the generator, and raise it
slowly at a completely vertical angle.
Personnel performing lifting work must wear protective gear such as helmets,
safety shoes and gloves.
Do not move the generator during operation.
(1) Lifting Procedures
Always be sure to use lifting hooks when lifting up the generator, and raise it slowly at a
completely vertical angle.
(2) Transport
When transporting this generator, tie rope to the left and right tie downs, and securely fix
the generator.
< Note >
Handle this generator with great care when raising, lowering and transporting. Rough handling of
generator can result in damage or malfunction.
Lifting
Hook
Tie-Down
3Way Fuel
Valve
External Fuel
Return
External Fuel
Inlet