28
Let engine idles for approximately 5 minutes.
Ensure that the tachometer shows the following frequency at no load.
No Load Frequency (Revolving Speed)
50Hz RUN
52.5Hz (about) (1575min
-
1
)
< Note >
By setting frequency to the above frequency under no load, 50Hz(almost)
will be obtained at the rated output load.
Adjusting the Voltage Regulate Dial, set it to the required voltage.
50Hz RUN
415V
Turn the circuit breakers to ON to send power to the load side.
WARNING : Electric Shock / Injuries
Before turning RCCB to ON to send power to the load side,
always ensure that any circuit breaker and switch of loads are positioned to
OFF.
In the case the generator and the load are away from each other, proceed
with the above steps, communicating well with the other person by the load
in order to prevent from accident.
6
7
8
9