29
9-2.
Procedures during Operation
(1) Checks after Startup
Make sure that the controller is in normal status.
Check that there is no abnormal vibration or noise.
Check that the exhaust gas color is normal. When operation is normal, the exhaust gas
should be colorless or slightly bluish.
< Note >
If abnormal, stop using this generator and request authorized distributor where the generator
was purchased to repair the generator.
(2) Adjustment during operation
During load operation, check the voltage on the Operation Display and finely adjust
voltage using the voltage regulator dial.
■
Extracting the air out of the fuelling system for engine stop due to no fuel.
This generator is equipped with automatic extracting feature.
Thus, if the engine stops due to running out of fuel, follow the next steps to extract
the air out.
Add fuel to the fuel tank.
Turn the Power Switch to AIR BLEEDING position. It will take approximately
30 seconds to extract the air out.
Press the Start Button, and confirm the engine has started properly.
< Note >
In the case air is in the fuel line, the engine speeds is unstable.
In the case, perform the vacuum again.
1
2
3