48(51)
Picture 6-10: Connection of Signal Wire
6) Connect signal wires of the transmitter and power lines of dew-point
monitor with the according terminals.
Connet contact No.1 and No.2 with power, supply is 220VAC.
Contact No.3, No.4 and No.5 are idle.
Connect contact No.6 and No.7 with the signal of transmitter. (C- Connects
contact No.6, C+ connects contact No.7
Dew-point transducer wiring (white connect to C-, blue connect to C+)
Picture 6-11: Connection of Dew-point Monitor
6.6.2 Dew-point monitor setting
1. Common mode functional setting (adjust dew-point alarm setting value):
1) Press
“
S
”
key to enter setting (after entering, the displayer flickers);
2) Adjust dew-point alarm setting value, and press
“
U
”
and
“
D
”
to adjust the