39(42)
SIC-10W
5.0
SIC-40W
20
SIC-12.5W
7.0
SIC-45W
25
SIC-15W
8.5
SIC-50W
34
Attention!
Don
’
t replace with other refrigerant without permission.
Don
’
t replace the components of the refrigerating system unauthorized.
The medium used is water. If you need to use other media, please consult
the manufacturer in advance.
6.2 Components Maintenance
6.2.1 Condenser
The SIC-W-R2 series of water chiller adopts tube-in-shell condenser, which will
have water scaleon the heat transfer tubes after long-term use or there will be
sundries blocked due to poor water treatment. The condenser must be cleaned
regularly, so that the machine can maintain its good working performance. If the
cooling water has been treated with water purification, it is recommended to use
hydrogen peroxide to sterilize and remove the algae, and then check whether
there is water scaleafter washing by the high-pressure water gun. If the cooling
water is not purified, it can be cleaned with citric acid or aminoxanthic acid and
corrosion inhibitor, and then washed with high-pressure water gun, which must be
passivated after acid pickling, and you can purchase the passivator for the
treatment.
Attention!
When machine shutdown or store unused in an environment with
temperature lower than 0
℃
, disconnect the pipeline, raise the front end of
the machine, and force to discharge the water in the condenser.