10(40)
1.3.2 Specification List
Table 1-2: Specifications List (1)
Model
Item/
Parameters
SIC-3A
SIC-5A
SIC-8A
SIC-10A
SIC-12.5A
SIC-15A
Refrigerant
Capacity
1)
kW
7.35
12.5
19.5
26
30
38
Kcal/hr
6,321
10,750
16,770
22,360
25,800
32,680
Compressor
Power(50H
z/60Hz)
kW
2.55/
3.96/
6.11/
8.06/
9.11/
11.8/
HP
3
5
8
10
12.5
15
Refrigerant
Weight (kg)
3.6
4.3
7
8
11
13
Control Mode
Thermostatic expansion valve
Type
R22
Evaporator
Type
Tube-in-shell style
Condenser
Type
Tube-fin style
Blower (kW)
(50Hz/60Hz)
0.18
0.45
0.25
×
2
0.45
×
2
0.6
×
2
0.78
×
2
Water Tank Capacity (L)
30
85
150
Pump
2)
(50Hz)
Power (kW)
0.75/0.75/1.1
1.1
1.1/1.5/2.2
(L/Min) Pump
Flow (L/min)
50/83/67
80/100/89
130/150/133
Working Pressure
(kgf/cm
2
)
2.0/2.6/3.8
2.0/2.6/3.5
2.0/3/4.2
Total Power (kW) (50Hz/60Hz)(kW)
3)
3.48
5.16
7.71
10.06
11.41
14.81
Pipe
Coupling (inch)
Cooling Water
Outlet
1
1
1
/
2
2
Cooling Water
Inlet
1
1
1
/
2
2
Water Tank Outlet
1/2
Water Tank Port
1/2
Protective
Devices
Compressor
Overload relay
pump
Overload relay
Cooling Water
Circuit
High and low pressure switch/anti-freeze switch
Water Circuit
Flow switch (optional) / water tank level sensor (optional) / bypass valve
Power(VAC)
4
)
3
Φ
,400V,AC 50HZ
Measures Exchange
1Kw=860 kcal/hr 1RT=3,024kcal/hr 10,000Btu/hr=2,520kcal/hr
We reserve the right to change
specifications without prior noice.
Note:
1) Refrigeration capacity is measured based on the flow 0.172 m
3
/ (h.k W) and the outlet temperature (7
℃
) of
chilled water under the environment temperature of 35
℃
.
2) Low pressure pump is for domestic and Southeast Asia export, customers can change for medium
pressure pumps (use P for short; e.g.: SIC-5A-P) or high pressure pumps (use HP for short; e.g.:
SIC-5A-HP), specific parameters in turn as shown above.
3) Pump power is included in total power.
4) Special orders of machine voltage can be acceptable according to customers
’
requests.