OPERATION CMT-240-K
5.4 Explanation of each setting display
h
Main setting value setting display
Sets the main setting value for all channels.
Setting range: Rated scale range of the CCT-235
Refer to the rated scale of the CCT-235
in the instruction manual for the C series.
h
Alarm 1
setting display
Sets the action point of Alarm 1 output for all channels.
However, the setting is not available for the channels
that No alarm is selected on the Alarm 1 action form
selection display (page 28).
Setting range: See [Table 5.4-1] below.
[Table 5.4-1]
Setting range
Alarm action form
TC
RTD or TC with decimal point
High limit alarm (with standby)
*
-200 to 200 ( )
-200.0 to 200.0 ( )
Low limit alarm (with standby)
*
-200 to 200 ( )
-200.0 to 200.0 ( )
High/Low limits (with standby)
*
0 to 200 ( )
0.0 to 200.0 ( )
High/Low limit range (with standby)
*
0 to 200 ( )
0.0 to 200.0 ( )
Process high alarm (with standby)
Input range minimum to input range maximum value
Process low alarm (with standby)
Input range minimum to input range maximum value
Setting range
Alarm action form
DC voltage, DC current
High limit alarm (with standby)
*
-2000 to 2000
Low limit alarm (with standby)
*
-2000 to 2000
High/Low limits (with standby)
*
0 to 2000
High/Low limit range (with standby)
*
0 to 2000
Process high alarm (with standby)
0 to 10000
Process low alarm (with standby)
0 to 10000
*
Setting the value to 0 or 0.0
disables the alarm action.