10
5.2 Main setting mode
Character
Name, Description, Setting range
Default
SV1
• Sets SV1 (desired value 1) of control.
• Setting range: SV low limit value to SV high limit value
0
( )
SV2
• Sets SV2 (desired value 2) of control.
• Available only when the [SM] option is added.
• Setting range: SV low limit value to SV high limit value
0
( )
5.3 Sub setting mode
Character
Name, Description, Setting range
Default
Auto-tuning/Auto-reset
• Sets auto-tuning (AT) or auto-reset.
• Auto-reset will be canceled automatically in approx. 4 minutes.
•
/
: Auto-tuning/Auto-reset Perform
/
:
Auto-tuning/Auto-reset Cancel
Proportional band
• Sets the proportional band of control output (OUT).
• ON/OFF action when set to 0 or 0.0
• Setting range: 0 (0.0) to Input range high limit value
10
(20 )
Integral time
• Sets the integral time of control output (OUT).
• Setting the value to 0 disables the function.
• With PD action (I=0), auto-reset can be performed.
• Setting range: 0 to 3600 seconds
200sec
Derivative time
• Sets the derivative time of control output (OUT).
• Setting the value to 0 disables the function.
• Setting range: 0 to 3600 seconds
50sec
Proportional cycle
• Sets the proportional cycle value of control output (OUT)..
• Not available for ON/OFF action or DC current output type
• Setting range: 1 to 120 seconds
R/ :
30sec
S/ :
3sec
Alarm value
• Sets the action point of the alarm output.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• Not available for the FCL-130.
• Not available if No alarm action is selected during Alarm type selection.
• Not available if the “Alarm” is not selected during Event output function
selection.
However, available when [C5] option is added.
• Refer to (Table 5.3-1).
0
( )
Heater burnout alarm value
• Sets the current value of Heater burnout alarm.
• Available only when the [W] option is added.
• Available only when the “Heater burnout alarm” is selected during
Event output function selection.
• Upon returning to set limits, the alarm will stop.
• Setting range:
Rated current 5A: 0.0 to 5.0A
Rated current 10A: 0.0 to 10.0A
Rated current 20A: 0.0 to 20.0A
Rated current 50A: 0.0 to 50.0A
0.0A