11
Loop break alarm time
• Sets the time it takes to assess the Loop break alarm.
• Not available for the FCL-130.
• Not available if the “Loop break alarm” is not selected during Event
output function selection.
However, available when the [C5] option is added.
• Setting range: 0 to 200 minutes
0 min.
Loop break alarm span
• Sets the span to assess the Loop break alarm.
• Not available for the FCL-130.
• Not available if the “Loop break alarm” is not selected during Event
output function selection.
However, available when the [C5] option is added.
• Setting range: 0 to 150
( ), or 0.0 to 150.0
( )
0
( )
(Table 5.3-1)
Alarm type
Setting range
Setting range
(with decimal point)
High limit alarm
-(Input span) to input span
-199.9 to input span
Low limit alarm
-(Input span) to input span
-199.9 to input span
High/Low limits alarm
0 to input span
0.0 to input span
High/Low limit range alarm
0 to input span
0.0 to input span
Process high alarm
Input range low limit to
input range high limit
Input range low limit to
input range high limit
Process low alarm
Input range low limit to
input range high limit
Input range low limit to
input range high limit
High limit alarm with standby
-(Input span) to input span
-199.9 to input span
Low limit alarm with standby
-(Input span) to input span
-199.9 to input span
High/Low limits with standby
0 to input span
0.0 to input span
High/Low limit range with standby 0 to input span
0.0 to input span
Process high alarm with standby
Input range low limit to
input range high limit
Input range low limit to
input range high limit
Process low alarm with standby
Input range low limit to
input range high limit
Input range low limit to
input range high limit